Electrical Troubleshooting MCQ Quiz Part 2 of 5 | 50 Questions
Electrical Troubleshooting MCQ Quiz — Part 2 of 5
Motors & Starters | 50 Practice Questions (Q51–Q100 of 250) | For ITI Electrician, Wireman, Diploma Electrical/EEE and industrial electrical maintenance trainees
Covers induction motor theory, DOL/star-delta starting, overload relays (including IEC 60947-4-1 trip classes), single-phasing, bearing faults, megger/insulation-resistance testing and insulation classes.
This is Part 2 of a 5-part, 250-question Electrical Troubleshooting practice series covering real-world fault-diagnosis scenarios.
About this practice set
This page is Part 2 of 5 in the Electrical Troubleshooting MCQ Quiz series. It contains 50 multiple-choice questions (Q51 to Q100 of the 250-question set) on Motors & Starters. The questions are written for ITI, diploma and B.Tech trainees and for anyone preparing for a maintenance or fault-finding interview. Each question has four options; the quiz above checks your answer and shows an explanation, and the full answer key is printed below so you can also revise without running the quiz.
How to use this quiz
- Attempt the questions in one sitting without searching for answers.
- Read the explanation shown after each answer, even when you were right.
- Write down the questions you missed and the reason in your own words.
- Open the answer key below to revise those questions.
- Retake the quiz after a day or two and compare your score.
Sample of what is covered
- The basic working principle of a three-phase induction motor relies on:
- The main purpose of a star-delta starter is to:
- The typical starting (inrush) current of a standard induction motor, compared to its full load running current, is approximately:
- If a running three-phase motor experiences single-phasing, the most likely consequence is:
- A megger (insulation resistance tester) is primarily used to:
- To reverse the direction of rotation of a three-phase induction motor, a technician should:
- Voltage unbalance across the three phases supplying an induction motor is particularly harmful because it:
- Shaft misalignment between a motor and its driven equipment (pump, gearbox, etc.) primarily causes:
Answer key with explanations (50 questions)
Q1. The basic working principle of a three-phase induction motor relies on:
A. A rotating magnetic field in the stator inducing current in the rotor by electromagnetic induction ✓ Correct answer
B. Direct electrical connections between stator and rotor windings
C. Permanent magnets fixed on the rotor
D. A commutator switching current direction in the rotor
Q2. The synchronous speed of a three-phase induction motor is calculated using the formula:
A. Ns = 120f / P ✓ Correct answer
B. Ns = f / 120P
C. Ns = P / 120f
D. Ns = 120P / f
Q3. Slip in an induction motor is defined as:
A. The relative difference between synchronous speed and actual rotor speed, expressed as a fraction of synchronous speed ✓ Correct answer
B. The difference between line voltage and phase voltage
C. The angle between stator and rotor windings
D. The ratio of starting current to full load current
Q4. Why does an induction motor never actually run at exact synchronous speed?
A. Because relative motion between the rotating field and rotor is required to induce the rotor EMF and current that produce torque ✓ Correct answer
B. Because the stator windings are designed to prevent it
C. Because the supply frequency is unstable
D. Because the rotor bars are non-magnetic
Q5. What is the key construction difference between a squirrel cage rotor and a slip ring (wound) rotor?
A. A squirrel cage rotor has short-circuited bars with no external connections, while a slip ring rotor has windings brought out via slip rings for external resistance control ✓ Correct answer
B. A squirrel cage rotor always runs on DC supply
C. A slip ring rotor has no bearings
D. A squirrel cage rotor requires brushes for operation
Q6. A Direct-On-Line (DOL) starter is most suitable for:
A. Relatively small motors where the high starting current does not cause unacceptable voltage dips or mechanical shock ✓ Correct answer
B. Only very large motors above 100 HP
C. Motors that must start with zero inrush current
D. Motors operating exclusively on DC supply
Q7. The main purpose of a star-delta starter is to:
A. Reduce the starting current drawn by the motor by initially connecting the windings in star before switching to delta ✓ Correct answer
B. Increase the starting torque of the motor beyond DOL levels
C. Convert a single-phase motor into a three-phase motor
D. Permanently run the motor in star connection at all times
Q8. Compared to DOL starting, a star-delta starter typically reduces the line starting current to approximately:
A. One-third (1/3) of the DOL starting current ✓ Correct answer
B. Two-thirds (2/3) of the DOL starting current
C. The same as DOL starting current
D. Ten times the DOL starting current
Q9. Compared to DOL starting, the starting torque produced by a star-delta starter during the star phase is approximately:
A. One-third (1/3) of the DOL starting torque ✓ Correct answer
B. Equal to the DOL starting torque
C. Three times the DOL starting torque
D. Double the DOL starting torque
Q10. In a star-delta starter, the timer's main function is to:
A. Control the time delay before switching the motor connection from star to delta after starting ✓ Correct answer
B. Measure the total running hours of the motor
C. Trip the overload relay after a fixed time
D. Control the motor's rotational direction
Q11. Star-delta starting can only be used on motors that are:
A. Designed to run normally in delta connection at the supply line voltage (i.e., dual voltage rated, e.g. 415/240V) ✓ Correct answer
B. Designed only for DC operation
C. Single-phase induction motors
D. Rated for star connection as their only operating mode
Q12. A major drawback of high inrush starting current in large motors on a weak supply network is:
A. It can cause a significant voltage dip, affecting other connected equipment ✓ Correct answer
B. It permanently increases the supply frequency
C. It automatically improves the power factor
D. It reduces the resistance of the supply cables
Q13. The typical starting (inrush) current of a standard induction motor, compared to its full load running current, is approximately:
A. 5 to 7 times the full load current ✓ Correct answer
B. Equal to the full load current
C. Less than the full load current
D. 50 times the full load current
Q14. The primary purpose of an overload relay in a motor starter is to:
A. Protect the motor from sustained overcurrent that could cause winding damage due to overheating ✓ Correct answer
B. Provide short-circuit protection against extremely high fault currents
C. Reverse the direction of motor rotation
D. Reduce the starting current of the motor
Q15. A common thermal overload relay operates on the principle of:
A. A bimetallic strip bending due to heat generated by excess current, which trips a mechanism ✓ Correct answer
B. A magnetic field instantly opening a contact at any current above rated
C. A timer counting down a fixed duration regardless of current level
D. A capacitor discharging to trigger a trip
Q16. An overload relay for a motor should normally be set to a current value:
A. Equal to the motor's rated full load current as given on its nameplate ✓ Correct answer
B. Double the motor's rated full load current
C. Equal to the motor's starting (locked rotor) current
D. Half the supply transformer's rated current
Q17. Overload relay trip Class 10 (per IEC 60947-4-1) means the relay is designed to trip within approximately:
A. 10 seconds at 6 times (600%) the relay's rated current ✓ Correct answer
B. 10 minutes at rated current
C. 10 seconds at rated current only
D. 10 hours at locked rotor current
Q18. Single-phasing of a three-phase motor refers to the condition where:
A. One of the three supply phases is lost while the motor continues to be energized on the remaining two phases ✓ Correct answer
B. The motor is intentionally run on single-phase supply by design
C. All three phases fail simultaneously
D. The motor's speed exactly matches synchronous speed
Q19. If a running three-phase motor experiences single-phasing, the most likely consequence is:
A. The remaining windings draw excessive current trying to compensate, causing overheating and possible winding burnout ✓ Correct answer
B. The motor speeds up beyond synchronous speed
C. The motor automatically switches to DC operation
D. The power factor immediately becomes unity
Q20. A common real-world cause of single-phasing in an industrial motor circuit is:
A. A blown fuse or a loose/burnt terminal connection on one incoming phase ✓ Correct answer
B. The motor being correctly earthed
C. The overload relay being set too high
D. Using a star-delta starter instead of DOL
Q21. Which protective device is specifically used to detect and prevent motor damage from single-phasing conditions?
A. A single-phase preventer / phase failure relay ✓ Correct answer
B. A capacitor bank
C. A step-down transformer
D. A soft starter's bypass contactor
Q22. Which of the following is NOT a typical cause of motor overheating?
A. Correct earthing of the motor frame ✓ Correct answer
B. Sustained overload beyond rated capacity
C. Blocked or dirty cooling fan/ventilation
D. Running on significantly unbalanced supply voltage
Q23. Unusual noise and excessive vibration in a running motor are most often early symptoms of:
A. Bearing wear or failure ✓ Correct answer
B. Correctly balanced power factor
C. Proper lubrication
D. Normal healthy operation
Q24. A common cause of premature motor bearing failure is:
A. Insufficient or contaminated lubrication combined with shaft misalignment ✓ Correct answer
B. Using the correct grease at recommended intervals
C. Operating the motor within its rated load
D. Proper alignment between motor and driven equipment
Q25. A megger (insulation resistance tester) is primarily used to:
A. Measure the insulation resistance between windings and the motor frame/earth ✓ Correct answer
B. Measure the exact running speed of the motor
C. Measure the motor's power factor directly
D. Measure the vibration amplitude of the rotor
Q26. For routine insulation resistance testing of a standard low-voltage (below 1 kV) motor winding, a commonly used megger test voltage is:
A. 500 V DC ✓ Correct answer
B. 50 V DC
C. 50,000 V DC
D. 5 V DC
Q27. A commonly applied rule of thumb for minimum acceptable insulation resistance of a motor winding is:
A. 1 megohm per kV of rated voltage, with an absolute minimum of about 1 megohm ✓ Correct answer
B. Exactly 1 ohm regardless of voltage rating
C. 1000 megohms regardless of voltage rating
D. Zero ohms for a healthy motor
Q28. Before performing an insulation resistance (megger) test on a motor, it is essential to:
A. De-energize and fully disconnect the motor from the supply and discharge any residual charge ✓ Correct answer
B. Keep the motor running at reduced speed
C. Increase the supply voltage to the motor
D. Short the earth terminal to the phase terminal
Q29. The Polarization Index (PI) of a motor winding is calculated as the ratio of:
A. The 10-minute insulation resistance reading to the 1-minute reading ✓ Correct answer
B. The 1-minute reading to the 10-minute reading
C. The starting current to the running current
D. The winding resistance to the insulation resistance
Q30. A motor with insulation Class F has a maximum allowable winding temperature (including ambient and temperature rise) of approximately:
A. 155°C ✓ Correct answer
B. 60°C
C. 500°C
D. 40°C
Q31. To reverse the direction of rotation of a three-phase induction motor, a technician should:
A. Interchange the connections of any two of the three supply phases to the motor ✓ Correct answer
B. Interchange the neutral and earth connections
C. Reduce the supply voltage by half
D. Swap the star and delta connections
Q32. In a single-phase capacitor-start induction motor, the starting capacitor's main function is to:
A. Create a phase shift between the start and run windings to produce starting torque ✓ Correct answer
B. Store backup energy in case of power failure
C. Improve the motor's insulation resistance
D. Act as the motor's earth connection
Q33. In a capacitor-start single-phase motor, the centrifugal switch's function is to:
A. Disconnect the starting winding/capacitor once the motor reaches a set percentage of running speed ✓ Correct answer
B. Continuously vary the motor's speed
C. Provide overload protection
D. Reverse the motor's direction automatically
Q34. IE3 (Premium Efficiency) motors compared to standard IE1 motors are designed primarily to:
A. Reduce energy losses and operating cost by improving overall motor efficiency ✓ Correct answer
B. Increase the motor's starting current substantially
C. Eliminate the need for an overload relay
D. Reduce the motor's rated power output
Q35. If supply voltage drops significantly while a motor drives a constant mechanical load, the motor's current will typically:
A. Increase, since torque and current must rise to compensate for reduced voltage at the same load ✓ Correct answer
B. Decrease proportionally with voltage
C. Remain completely unchanged
D. Drop to zero immediately
Q36. Running an induction motor continuously at significantly below its rated voltage typically leads to:
A. Increased current draw, higher heating, and reduced starting torque ✓ Correct answer
B. Improved efficiency and cooler operation
C. No change in operating characteristics
D. Automatically corrected power factor
Q37. Voltage unbalance across the three phases supplying an induction motor is particularly harmful because it:
A. Causes a disproportionately large increase in current in one or more phases, leading to localized overheating ✓ Correct answer
B. Has no measurable effect on motor operation
C. Always improves the motor's power factor
D. Increases the motor's insulation resistance
Q38. A three-phase motor that hums loudly but fails to start when switched on is most likely suffering from:
A. Single-phasing, a mechanically jammed shaft, or an open winding preventing torque development ✓ Correct answer
B. A perfectly balanced three-phase supply
C. An overload relay set too high
D. Excess insulation resistance
Q39. A locked rotor test on an induction motor is performed to determine:
A. The starting current and torque characteristics of the motor with the rotor held stationary ✓ Correct answer
B. The no-load speed of the motor
C. The motor's insulation resistance at rated voltage
D. The exact bearing temperature under normal running
Q40. A no-load test on an induction motor is primarily used to determine:
A. Core losses and magnetizing current of the motor ✓ Correct answer
B. The motor's full load starting torque
C. The insulation resistance of the stator winding
D. The exact locked rotor current
Q41. In a typical DOL starter panel, the combination of a contactor and an overload relay serves to:
A. Switch the motor on/off (contactor) while continuously monitoring current for overload protection (overload relay) ✓ Correct answer
B. Provide only short-circuit protection with no overload function
C. Convert AC supply to DC for the motor
D. Replace the need for any circuit breaker upstream
Q42. In a star-delta transition, proper interlocking ensures that:
A. The star contactor fully opens before the delta contactor closes, preventing a short circuit across the supply ✓ Correct answer
B. Both star and delta contactors remain closed together permanently
C. The delta contactor closes before the star contactor opens
D. The overload relay is bypassed during transition
Q43. Shaft misalignment between a motor and its driven equipment (pump, gearbox, etc.) primarily causes:
A. Increased vibration and accelerated bearing wear on both machines ✓ Correct answer
B. Improved insulation resistance of the motor windings
C. A reduction in motor starting current
D. Automatic correction of the power factor
Q44. Vibration analysis is used in motor predictive maintenance mainly to:
A. Detect developing mechanical problems like bearing wear, imbalance, or misalignment before they cause failure ✓ Correct answer
B. Measure the motor's insulation resistance
C. Directly measure the motor's power factor
D. Replace the need for overload protection
Q45. The squirrel cage rotor is widely preferred in industrial induction motors mainly because it is:
A. Simple, rugged, low-maintenance, and requires no external electrical connections or brushes ✓ Correct answer
B. The only rotor type capable of variable speed operation
C. Cheaper but far less reliable than a wound rotor
D. Only suitable for single-phase applications
Q46. Motor rewinding becomes necessary when:
A. The winding insulation has failed or degraded beyond repair, often due to overheating or moisture ingress ✓ Correct answer
B. The motor's overload relay trips occasionally under genuine overload
C. The motor's terminal box cover is slightly loose
D. The motor bearings need routine greasing
Q47. In a Totally Enclosed Fan Cooled (TEFC) motor, the external fan mounted on the shaft primarily serves to:
A. Blow cooling air across the finned motor frame to dissipate heat from the enclosed windings ✓ Correct answer
B. Generate additional electrical output
C. Cool only the terminal box
D. Act as a backup bearing
Q48. An IP55 rating marked on a motor nameplate indicates that the motor enclosure provides:
A. Protection against dust ingress and low-pressure water jets from any direction ✓ Correct answer
B. Complete submersion protection underwater indefinitely
C. No protection against dust or water at all
D. Protection against dust only, with no water protection
Q49. An anti-condensation space heater is sometimes fitted inside idle standby motors mainly to:
A. Prevent moisture condensation inside the windings during long periods of non-operation ✓ Correct answer
B. Increase the motor's running speed when started
C. Replace the need for insulation resistance testing
D. Reduce the motor's starting current when it is eventually started
Q50. Compared to grease lubrication, a key characteristic of oil-lubricated motor bearings is that they:
A. Are typically used in larger or higher-speed machines and require a defined oil level/circulation system ✓ Correct answer
B. Never need to be checked or topped up
C. Cannot be used in any industrial motor
D. Provide no lubrication benefit at all
Frequently asked questions
Who is this Electrical Troubleshooting quiz for?
It is for ITI, diploma and B.Tech students, apprentices and working technicians who want to test fault-finding knowledge. The explanations are written to teach the reason, not just the answer.
How should I use the answer key?
Attempt the quiz first without looking. Then open the answer key, read the explanation for every question you missed, and retake the part after a day to see whether the explanation stuck.
Do I need to finish all five parts?
No, but the parts build on one another: fundamentals first, then components, then circuits and real-world scenarios. Part 5 is the best test of whether you can apply the earlier parts to a live fault.
Comments
Post a Comment